Pages

Friday, July 1, 2011

MedicalConspiracies- Dismantle the national power grid entirely, Why?



-------- Original Message --------
Subject: [Paranormal_Research] Electrical grid - why are they messing with it?...
Date: Fri, 1 Jul 2011 00:53:05 +1200 (NZST)
From: Misty <misty8@xtra.co.nz>
Reply-To: Paranormal_Research@yahoogroups.com




Subject: ...electrical grid - why are they messing with it?...
Date: Thursday, 30, June, 2011, 3:56 PM

http://www.degaray.com/pic/139_UdatedScrnshot.jpeg

29June2011
Jim Stone -

Permalink
POWER GRID TAMPERING WILL END AN ERA
See the update, which answers a question about DC connected main lines below this report.

A recent AP report states that there is a proposal in place to change the frequency various parts of the national electrical grid run at. The frequency differences will be minor, but will force an end to the national grid as we know it. The only way frequencies can be different at all in separate locations around the nation is to not have a grid at all.

They are attempting to childishly play this down as something that will mess up clocks. But what it really means is that they are going to dismantle the national power grid entirely.

And now I will dissect and shred this article

First of all, they are saying that this is going to be a "year long experiment". It won't be. Since dismantling the grid amounts to an act of war, once it is dismantled we will not get it back. This "experiment" is exactly what you would want to do to a nation as a pre-emptive measure before attacking it. When destroying a nation, the basics have to go. You need to destroy the water, electrical, and food supplies to force people to surrender. By running different frequencies in different parts of the grid,the laws of physics clearly dictate that it has to be run in sections, all isolated from each other.

Many readers know that one of the strengths of the internet is it's distributed data paths, which make it very difficult to take down. If a line gets cut, you can just re-route through a different line, and all is well. Our interconnected power grid, which has been in place and running synchronously with perfect phase and frequency matching across it's entireity since 1930, is an electrical equivalent of the internet, and is a marvel of the world.

Our intact electrical grid will feed power to areas that have lost it, and keep their lights on. So let's say a hurricane takes out Louisiana and all their generating facilities are damaged - the grid will provide power from Texas to help them get back on their feet. If you want to knock out power in a war, you would need to isolate Louisiana FIRST so that Texas could not feed them after you destroyed their infrastructure. This is the only truthful reason why anyone would suggest dismantling one of our greatest national treasures.

We have in America a system which would allow Hoover dam to provide power to Boston. But those days have to end before an experiment like the one this article discusses can even happen. Here is why:

The article states: "The group that oversees the U.S. power grid is proposing an experiment would allow more frequency variation than it does now without corrections, according to a company presentation obtained by The Associated Press".

Here they say they will allow "more frequency variation". Well, that means that after most of a century of having zero frequency variation, that there will now be frequency variation. America's power grid has been perfectly synchronized since 1930 and has never varied by more than 1/10th of a cycle (1/600th of a second) from coast to coast in over 80 years. This is due largely to the fact that the grid causes generating facilities to lock into each other, and mimic each other's phasing exactly. Any deviation in any one facility against the predominant phasing of the grid will cause it to lose efficiency and in extreme cases be destroyed.

To say they will allow "MORE frequency variation" is a lie, because it implies there WAS frequency variation. THERE NEVER WAS, EVER. That is why clocks have used the grid frequency as a reference for 4 generations.

Folks, you cannot have any frequency variation on an interconnected electrical grid. This is because our 60 hz AC is a rising and falling wave form which goes from negative to positive 60 times a second. Negative and positive ALWAYS have to line up. If you deviate from a 60 hz frequency by even 0.001 hz on only one part of the grid, all it will take is ten seconds for that variation in frequency to cause it to begin rising and falling opposite to the rest of the grid. That would represent a positive to negative electrical short right from within the fabric of the grid itself. So there is no such thing as a "slightly faster running grid" out east, it's a bold faced lie completely counter to the laws of physics.

HERE IS ANOTHER LIE TO SHRED:

"The North American Electric Reliability Corp. runs the nation's interlocking web of transmission lines and power plants."

No they don't. No one company manages the grid. It is managed via cooperation and understanding of the laws of physics. This company is merely now the face of the lie. The fact that they have a long history has been SHREDDED by this proposal of theirs, buisnesses come and go, and these people need to head on out the door.

I myself have had to make calls for power allocations to avoid regional black-outs when demand was predicted to be high, and I certainly never called these folks! I just called the facility feeding us and THEY handled it. If they could not handle it, they had the power routed from another area. So for the North American Electric Reliability Corp. to say they manage it all is quite a statement! How do we know they are not a front company, set up as a bogus pre-paid corporation with a purchased "history"? I have a LOT of experience, and NEVER HEARD OF THEM.


And now the math, which proves them liars.
Here is how you prove that the real goal is to dismantle the grid.

Their claim was that they wanted an allowed deviation of 20 minutes per year on one coast in comparison with the opposite coast. So let's take 20 minutes and multiply it by 60 seconds. That's 1200 seconds. Then divide that by days in a year (365) which will give you 3.287 seconds of deviation PER DAY. Take that number and divide it by hours (24) and that gives you a deviation of 0.136 seconds per hour. Divide that by 60 minutes and the deviation is 0.0022826 seconds per minute. Divide that by 60 again. That gives you a deviation of 0.000038 seconds per second. Now MULTIPLY that by your cycles PER SECOND, which is 60. Right back to 0.0022826 phase difference per second.

Now here is where it gets interesting. Let's say I am running a 600,000 volt line. Since the frequency we are dealing with is 60 Hz, it fits perfectly into the equation. Multiply 0.0022826 as a representation of percentage by 600,000 volts. AC has a positive and negative cycle which effectively doubles that rate, for a total of 0.0045652% per second. Multiply that by 600,000 volts, and the voltage creep equals 2739 volts per SECOND. The math is pretty simple from there. One minute (60 seconds) x 2,739 volts will equal a 164,347 volt difference in phasing between interconnected coasts per minute. Major problems will happen within 15 seconds. Total phase desynchronization will occur in a little under three minutes.

This serves to prove that no frequency deviation at all can be tolerated in an interconnected grid and that this agency - the so called "North American Electrical Reliability Corp" is lying out their butt in this news release and therefore can only have been usurped by either paper trained idiots or an enemy that wants an end to the American power grid, because allowing "frequency variation" can mean only that. The AP article should finish them, OUT OF BUSINESS.

The bottom line? The American power grid, at no time ever in the last 80 years has ever been out of synchronization, by more than 0.001 second total per year coast to coast. The laws of physics will not allow it. We cannot allow ANYONE to disconnect our grid. 20 minutes a year would not cut it in tuvalu! Not even 1/60th of 1 second would. It is a mathematical impossibility to have ANY deviation on an interconnected grid.

And it gets worse . . . . .

When it comes to phase correlation, momentum can be the enemy.

The generators at electrical facilities are ENORMOUS. People may not realize how big they really are. Large electrical facilities need to be spun up before going online, it takes a long time to get the enormous mass of the generator moving and stabilized, sometimes even hours. Even modest generators are so big that the spinning mass can weigh hundreds of tons, and surface speeds of the armatures can be over 100 MPH. That's a LOT of speed on a LOT of mass. The massive size of these generators helps them be perfectly stable when running. There is so much momentum built up in a large industrial generator that even enormous peak draws from it can be soaked up without it being perceptibly slowed by the peaks at all.

If an enemy was running the government then, and people were happy to have frequencies changed for no good reason at all, electrical "tug of wars" between generators could be set up under the premise of "oops" to destroy them. Breaker disconnects under such situations are often unsuccessful due to contacts getting welded. I have seen problems happen in even tiny one megawatt units, where a controller malfunctioned and dropped them onto the same line when their phasing was only off by a fraction of a percent.. One was going very slightly ahead the other, so it drove the other to go faster while the other slowed it down. The over-reactions were extreme; they ponged each other's speed up and down and the accelerations/decelerations were enormous, taking place within fractions of a second. I fully expected the windings to explode. I was blown away by how extreme their behavior was.

Even a pair of small generators can be caused to totally freak out from an initial phasing difference that is very minor. This problem would be greatly exacerbated in a power play between multiple enormous generators. Electrical explosions would no doubt result, in the case I witnessed, they both got the right bounce within a couple seconds and stabilized. It was a brief and exciting event. Things are normally not so lucky and the answer is obvious - If you want no problems in the electrical grid, a perfect standard frequency should be the norm, as it always has been for over 80 years.

However, if you were an enemy in posession of a virus like Stuxnet, a non-interconnected grid with all the switch gear from when it was previously connected still in place to play with could be lots of FUN!. To blow out two regions at the same time, all you would have to do is activate switch gear that is already in place from the old grid when both regions are out of phase with each other. Doing so would cause serious damage to equipment in both regions.

Want to blow a nuclear reactor? Here's a good way to try! SUDDENLY and without announcement, introduce a frequency difference on the grid.. Suddenly that nuke plant would be forced to deal with a rapid phase inversion on the grid. With all the stored momentum in the generators available for a nice peak surge output, thousands and thousands of times higher than anything they could ever handle if suddenly the coupled phases were inverted, there would be at a minimum enormous explosions in the circuit breakers and switch gear, and most likely enormous explosions from within the generator windings themselves.

Suddenly, with the windings and switch gear blown in an instant, there would be nothing left to load the generator, which needs to be held back from accelerating by the electrical system it is feeding power into. You would get a brief period of rapid acceleration before safety shutoffs re-routed steam from the generator's turbines to an emergency bypass. Things would get sketchy after this. YOU NEED TO GET RID OF THAT STEAM.

At a minimum, safety valves should open on the reactor or whatever else (coal fired boiler) to release the sudden steam pressure buildup resulting from the turbine steam not being needed anymore. If the system was infected with Stuxnet, (85 percent of our power generating facilities can be) and Stuxnet was programmed to over ride the emergency steam release valves as was the case at Fukushima, things WILL explode. Said explosions would not be minor. The worst possible case scenario would be a nuclear reactor which was running at full output suddenly not having it's steam be needed anymore, be kept at full thermal output by a virus that also forces all the safety related equipment to not activate.

Clandestine military action is the only reason any thinking engineer would want to suggest acceptance of variances in the grid frequency. There is no possible way to derive any sort of benefit from not keeping the frequency dead on, as it has always been.

But it gets worse, even

Every motor powered device depends upon the grid frequency to regulate how hard it runs itself. All of the design characteristics involving material stress and current draw are centered around an always reliable 60 hz frequency. If the frequency was increased to 70 hz, swamp coolers would burn up from trying to run too fast, as would air conditioners, washing machines, ect. The amount they are talking about in the article would not be that high, but I believe it is the end goal and introducing the concept of tampering with the frequency is like a toe dip to see if there are any pihranas out in the public sphere to look out for while they slowly weaponize the power grid. I will happily provide the first bite. What if they choose 90 hz? 100hz? Not much would survive that, and whatever did would not be the same anymore. Welcome to the third world.

Here is a great quote to rip, this is an outright lie

Some parts of the grid, like in the East, tend to run faster than others. Errors add up. If the grid averages just over 60 cycles a second, clocks that rely on the grid will gain 14 seconds per day, according to the company's presentation."

There is zero frequency variation on the grid between east and west coasts. It is physically impossible for them to vary by even 1/10th of a cycle (1/600th of a second) per year. ANY drift will cause immediate phase cancellation with other parts of the grid resulting in immediate grid failure.

This entire report is such a bold faced stream of BS and lies, I am blown away to think they would ever consider trying. This is downright brazen

I know many readers believe the end is near for this nation.. Proposals like this prove it. Even worse is the attitude of AP. Did they not consult anyone who actually knew what this would do, other than the enemy? Are THEY the enemy?

They will do this if we do not speak up. If you want this nation to have a future, I strongly suggest you make it perfectly clear that the GRID IS NOT TO BE TAMPERED WITH.

UPDATE:

 

These comments are in response to people who e-mailed me telling me the grid was now running DC, which would, if true, make my main premise irrelevant.

My response follows

I know that on many of the big transmission lines they are indeed using DC on VERY LONG RUNS of 400 miles or more because it allows higher RMS throughput and minimizes inductive losses, but it is not always the case. None of the big lines in my area are that way, and AC distribution is still so predominant that playing with frequencies on a grid as great as ours is the equivalent of handing a ferarri over to a tinkering teenager. I will not budge on my major premise, that phase conflict issues will indeed force the grid to operate in isolated pockets if an experiment with different AC frequencies is allowed, and that anyone is suggesting it should be allowed to run with frequency variations should be the subject of GREAT scrutiny and suspicion.

How much of the grid, exactly, uses DC/inverter arrangements? VERY LITTLE. And it is ALL on remotely situated lines of enormous length. You will find few of these types of lines if ANY east of the Rockies. These are mostly in the desert southwest. East of the rockies, where long runs are not needed, whether or not DC will save you money has to be calculated against cost of equipment and losses of power in that equipment. Rectifiers and inverters do not run with perfect efficiency, there are losses and if those losses add up to more than what the AC inductive losses over a stretch of line would be it makes no sense at all to use them. Furthermore, if an arc ever starts on a DC line, there HAS TO be a short power outage to extinguish it. AC lines usually self extinguish in one cycle automatically. Bye bye birdie and the only worry is a wild fire.

Despite a few people saying DC makes my suspicions irrelevant, upon checking for recent technology changes I found I am completely correct and I am not budging on my main premise - that there is no rational reason to tamper with the grid frequency.

Also:

Phasing is everything. Get more than 30 degrees before or behind the phase and you are toast. If you do not understand why frequency matters, stay off the subject. It's not a matter of ideal or not ideal, it's a matter of POOF!. You may think you are doing a service by going around telling people I am full of BS, but it is very common for electricians to not understand what functions frequency performs and beyond virtually all of them to understand that you cannot have two dominant frequencies from different sources on the same line without encountering severe problems.

 

Frequency matters a LOT MORE THAN VOLTAGE, INFINITELY MORE because excess voltage does not go on a continuously proceeding march forward. A high voltage on a line will stay where it is, but a different frequency will walk forward on a phase until it lands directly opposite. Things will trip out long before that happens. Any frequency deviation between two signal sources will put one source wave form negative to the other source positive very rapidly. A full phase misalignment will represent an RMS voltage difference between both sources that is TWICE the RMS voltage of each source if they are the same voltage to begin with, and they are 180 out from each other. Yes I know 3 phase is 120 degrees per phase but I was not all too excited about trying to explain three phase power in an article mostly read by people who do not deal with electricity.

I have seen countless electricians mistake harmonics for "frequency variation" and then run around saying the place runs on "70 HZ!". Harmonics can be pesky, but they are NOT the root frequency, and if your meter is telling you there is 70 hz on a 60 hz line, there is either a severe overspeed on your generator or you are picking up a harmonic. Suspect a harmonic. Meters will often do that, and it has nothing to do with root frequency. Not understanding this is very common among average electricians.

My reference was for single phase AC because I did not want to try to explain 3 phase power to average people. My report was not written for electricians, it needs to hit the masses to make a difference.

I am dead right about inverted phases and frequency creep, interconnected systems have to hit the EXACT SAME FREQUENCY DEAD ON, even being off a fraction of a percent will quickly be the equivalent of shorting opposite phases.

Leading the phase and lagging the phase DOES NOT CONSTITUTE A FREQUENCY DIFFERENCE. Lots of places might try pushing the phase to get more power out or correct a lagging power factor. That is not the same thing as producing a different frequency altogether. That is something I did not put in the report because it is far too complex for average people but I know there are plenty of electricians out there who actually think that pushing the phase requires you to run at a higher frequency; it does not. It changes the shape of the ouput wave form and that is all.

I am sure there are a few who will comment about the fact that capacitors are used to correct a lagging power factor, but there are many ways to do it. Capacitors are ONE WAY to correct lagging power factors but when it comes to heavy duty correction, they are lacking compared to running a synchronous motor with an over excited field or a generator dedicated to pushing the lag forward. Linemen do not come across anything other than capacitors. There are other ways.

And even if short distribution lines were running inverter only,

For what reason would we have to accept frequency inaccuracies amounting to 14 seconds a day? Cheap dollar store watches can hit that accuracy, so what plausible reason could be offered to support accepting it when any inverter used on a distribution line would cost hundreds of thousands of dollars? Can't put a $30 part in it to keep the frequency to within a half second a day? HOGWASH! They ALL have the ability to output very accurately. Nowadays we should be demanding a MORE ACCURATE GRID FREQUENCY, if it could be done; IT CANNOT.

Don't allow scammers to "fix" what is not broken!


source

 

{{  http://www.degaray.com/misc/139_JimStonePowerGridTamperingEndsAnERA.html  }}

No comments:

Post a Comment

Note: Only a member of this blog may post a comment.